AC3000 series interrow air cooled air conditioner(12KW~65KW)

AC3000 series interrow air-cooled air conditioner is a cooling, efficient, energy-saving precision air conditioner for the room, which is suitable for the micro-module data center with high temperature or humidity control precision and high sensible heat requirements. The inter-column air conditioner is placed in the rack arrangement and installed side by side with the server cabinet. The air is discharged from the front of the unit, and the air is returned at the rear. It is close to the heat source and cooled at the near end. It can meet the environmental control requirements of various equipment rooms in different regions. All air-cooled products are equipped with R410A refrigerant type DC inverter scroll compressor, which is highly efficient and energy saving.

  • Efficient and reliable

    Adopt permanent magnet synchronous DC brushless frequency conversion, low noise, small vibration scroll compressor, can automatically adjust the cooling capacity according to the dynamic load of the machine room 10%-100%; The unit is equipped with a standard gas-liquid separator to separate the liquid refrigerant before the compressor suction port to prevent the compressor “ Liquid hammer ” .

  • Energy efficient

    The unit adopts inverter scroll compressor, can choose the inverter compressor scheme; High performance EC centrifugal fan, large air volume, high static pressure, smooth operation, low noise; Fully enclosed electronic expansion valve control, accurate adjustment, to ensure the stability of refrigerant flow, reduce temperature fluctuations in the equipment room; The outdoor fan adopts stepless variable speed regulation technology to ensure stable operating pressure and reduce unit energy consumption.

  • Intelligent control

    Intelligent controller for PID operation, automatic adjustment of compressor and fan speed; The compressor speed can be automatically adjusted between 1800 and 7000RPM; The standard RS485 communication interface can realize coordination and linkage with external devices, and help the entire air conditioning system in the computer room intelligent and energy-saving control.

Application scenario

  • Computer Room
    Data centers with high heat density and low PUE value requirements, computer rooms

  • System Room
    Such as supercomputing center, data center, cloud computing center, communication room, switching room, transmission room, electronic information system room

  • Data Center
    Integrated Micromodule Data Center

  • Precision Environment
    Precision environments such as container data centers
The air conditioner in a small equipment room is suitable for places that have high requirements on ambient temperature and humidity. High heat density, low PUE value requirements for data centers, computer rooms.
Such as supercomputing center, data center, cloud computing center, communication room, switching room, transmission room, electronic information system room.  
Integrated micro-module data center, container data center and other precision environment.
    Technical specification

    Model AC3000-12 Series AC3000-25 Series AC3000-35 Series AC3000-40 Series AC3000-50 Series AC3000-65 Series
    Indoor return air condition: 37.8℃ DB/ 20%RH; Outdoor conditions (air cooling) : 35℃
    Cooling capacity (kw) 14.7 26.3 36.2 43.7 54.5 65.6
    Cooling capacity (kw) 14.7 26.3 36.2 43.7 54.5 65.6
    Indoor return air condition: 37℃ DB/ 24%RH; Outdoor conditions (air cooling) : 35℃
    Cooling capacity (kw) 14.5 26 35.8 43.1 53.3 65
    Cooling capacity (kw) 14.5 26 35.8 43.1 53.3 65
    Indoor return air condition: 35℃ DB/ 30%RH; Outdoor conditions (air cooling) : 35℃
    Cooling capacity (kw) 13.3 25.1 35.8 42 52.2 62.1
    Cooling capacity (kw) 13.3 25.1 35.8 42 52.2 62.1
    Function Optional constant temperature and humidity function
    Electric heating capacity (kw) 1 1 4 6 6 6
    Humidification capacity (kg/h) 1.5 1.5 1.5 3 3 3
    Humidification method Wet film humidification
    Indoor unit air volume (m³/h) 2700 5000 6000 8500 10500 12000
    Number of indoor fans 4 5 7 3 3 3
    Indoor unit power supply (V/PH/Hz) 3N+PE ~ 380V 50Hz
    Indoor unit size: Width * Depth * Height (mm) 300*1200*2000 300*1200*2000 300*1200*2000 600*1200*2000 600*1200*2000 600*1200*2000
    Indoor unit weight (kg) 255 300 250 350 380 400
    Outdoor unit weight (kg) 83 115 168 135 195 234
    主站蜘蛛池模板: 日本强伦姧熟睡人妻完整视频 | 色综合h| 国产免费观看黄A片又黄又硬小说 | 亚洲 欧美 在线观看 | 久久99精品久久久久久首页 | 亚洲一区二区三区免费看 | 高清无码v视频日本www | 国产精品香蕉在线一区二区 | 日韩精品久久久肉伦网站 | 日本欧美不卡一区二区三区在线 | 成人黄色在线免费观看 | 色情A片成人网站免费看 | 热99re6久久精品 | 搡老女人免费视频 | 婚后1v1啪啪做H高甜 | jizz韩国 | 天天干天天干天天插 | 狠狠亚洲丁香综合久久 | 九九九日产 | 丁香花在线观看免费观看 | 五月天六月丁香 | 免费无码又爽又黄又刺激网站 | 国产激情视频网站 | 亚洲女bbwxxxx另类 | 春色 都市 亚洲 小说区 | 日韩一区二区免费视频 | 色综合站 | 国产黄色片免费看 | 国产自产一c区 | 国产无遮挡色视频免费观看性色 | 在线观看免费视频污网站 | 影888午夜理论不卡 樱井莉亚快播 | 2024国产精品视频一区 | 日本免费在线一区 | 日本韩国免费视频在线 | 久久成人麻豆午夜电影 | 日本高清视频在线无吗 | 男人晚上适合偷偷看的污污 | 亚1州区2区3区产品乱码 | 影音先锋男人站 | 一本色道久久综合狠狠躁篇 |