AC5000L-39 series chilled water column precision air conditioner

AC5000L-39 series chilled water row precision air conditioner is a cooling, efficient and energy-saving precision air conditioner for computer rooms, which is suitable for micro-module data centers with high temperature or humidity control precision and high sensible heat requirements. The chilled water inter-row air conditioner is placed in the rack and installed side by side with the server cabinet. The air is discharged from the front of the unit, and the air is returned from the rear. The air is cooled near the heat source, and the cooling efficiency is high.

  • Safe and reliable

    Green, safe and reliable; The use of chilled water as a refrigerant is the closest to the natural air conditioning method, green, healthy, environmental protection; High performance EC centrifugal fan, large air volume, high static pressure, smooth operation, low noise; Perfect automatic alarm and diagnosis function, all-round protection of air conditioning units, but also more effective to prevent failure, extend the service life of air conditioning units.

  • Energy efficient

    Large flow coefficient of proportional integration electric two-way valve, real-time regulation system water flow; Refrigeration near the heat source, short airflow path, small cold loss; Maximize the use of the space inside the unit to improve the heat exchange area, better heat exchange effect, higher machine performance; The unit uses copper tube hydrophilic aluminum fin heat exchanger, which has high heat density and higher heat exchange efficiency.

  • Intelligent control

    Intelligent controller for PID operation, automatic adjustment of water saving valve opening and fan speed; The control mode can be freely selected for return air temperature control or supply air temperature control; The standard RS485 communication interface can realize coordination and linkage with external devices to help the entire room air conditioning system intelligent and energy-saving control.

Application scenario

  • Data Center
    Such as supercomputing center, data center, cloud computing center, communication room, switching room, transmission room, electronic information system room

  • Integrated Micromodule Data Center

  • Precision environments such as container data centers
The air conditioner in a small equipment room is suitable for places that have high requirements on ambient temperature and humidity.
Data centers with high heat density and low PUE values, computer rooms. Such as supercomputing center, data center, cloud computing center, communication room, switching room, transmission room, electronic information system room integrated micro-module data center. Precision environments such as container data centers.
    Technical specification
    Model AC5000L-39 Series
    Function Optional constant temperature and humidity function
    Return-air condition 37℃/24%
    Main Power supply 220V/50Hz
    Chilled water inlet and outlet temperature (℃) 15/21 12/18 10/15 7/12
    Total cooling capacity (kw) 27.3 31.8 34.7 42.0
    Net cooling capacity (kw) 27.3 31.8 34.7 39.0
    Water flow (m³ /h) 3.9 4.4 5.9 7.1
    Heating capacity (kW) 3.0
    Humidification capacity (kg/h) 3.0
    Water resistance (kPa) 18.2 23.0 40.0 58.0
    Circulating Air Volume (CMH) 5500
    Number of fans 6
    Size: Width * Depth * Height (mm) 300*1200*2000
    主站蜘蛛池模板: 国产男女猛烈无遮挡A片软件 | 大量国产激情视频在线观看 | 国产第一页浮力影院草草影视 | 久久是热频这里只精品4 | 国产福利视频在线精品 | 欧美与黑人午夜性猛交久久久 | 色中色最新网址 | 人人97| 性一交一乱一乱A片AP88 | 婷婷丁香视频 | 麻豆专媒体一区二区 | 欧美人妖20p | 亚洲日本在线观看 | 欧洲男女下面进出的视频 | 久久99AV无色码人妻蜜柚 | 高清一区二区不卡视频 | 亚洲二区在线 | 国产丰满人妻一区二区三区 | 被少妇滋润了一夜爽爽爽小说 | 久久视频在线视频精品 | 中文字幕亚洲男人的天堂网络 | 在线观看日本污污ww网站 | 亚洲精品欧美精品 | 99re66精品视频在线观看 | 波多野中文字幕s | 久久99精品久久久久久三级 | freev de0x x性欧美f | 99精品久久久久久国产人妻 | 最新国产三级 | 一本久久综合亚洲鲁鲁五月天 | 新版天堂资源在线官网8 | 五月香六月婷婷激情综合 | 亚洲精品中文字幕无码A片老网站 | 中文字幕在线观看不卡 | 日本黄色成年人免费观看 | 国产人妻人伦精品98 | 日本妇人成熟A片高潮小说 日本高清免费观看高清电影 | 狠狠干一区 | 舔弄bb | 福利片导航| 簧片电影大全网站 |