AC5000L-81 series chilled water column precision air conditioner

AC5000L-81 series chilled water row precision air conditioner is a cooling, efficient and energy-saving precision air conditioner for computer rooms, which is suitable for micro-module data centers with high temperature or humidity control precision and high sensible heat requirements. The chilled water inter-row air conditioner is placed in the rack and installed side by side with the server cabinet. The air is discharged from the front of the unit, and the air is returned from the rear. The air is cooled near the heat source, and the cooling efficiency is high.

  • Safe and reliable

    Green, safe and reliable; The use of chilled water as a refrigerant is the closest to the natural air conditioning method, green, healthy, environmental protection; High performance EC centrifugal fan, large air volume, high static pressure, smooth operation, low noise; Perfect automatic alarm and diagnosis function, all-round protection of air conditioning units, but also more effective to prevent failure, extend the service life of air conditioning units.

  • Energy efficient

    Large flow coefficient of proportional integration electric two-way valve, real-time regulation system water flow; Refrigeration near the heat source, short airflow path, small cold loss; Maximize the use of the space inside the unit to improve the heat exchange area, better heat exchange effect, higher machine performance; The unit uses copper tube hydrophilic aluminum fin heat exchanger, which has high heat density and higher heat exchange efficiency.

  • Intelligent control

    Intelligent controller for PID operation, automatic adjustment of water saving valve opening and fan speed; The control mode can be freely selected for return air temperature control or supply air temperature control; The standard RS485 communication interface can realize coordination and linkage with external devices to help the entire room air conditioning system intelligent and energy-saving control.

Application scenario

  • Data Center
    Such as supercomputing center, data center, cloud computing center, communication room, switching room, transmission room, electronic information system room

  • Integrated Micromodule Data Center

  • Precision environments such as container data centers
The air conditioner in a small equipment room is suitable for places that have high requirements on ambient temperature and humidity.
Data centers with high heat density and low PUE values, computer rooms. Such as supercomputing center, data center, cloud computing center, communication room, switching room, transmission room, electronic information system room integrated micro-module data center. Precision environments such as container data centers.
    Technical specification
    Model AC5000L-81 series
    Function Optional constant temperature and humidity function
    Return-air condition 37℃/24%
    Main Power supply 380V/3p/50Hz
    Chilled water inlet and outlet temperature (℃) 15/21 12/18 10/15 7/12
    Total cooling capacity (kw) 60.5 65.0 73.0 86.1
    Net cooling capacity (kw) 60.5 65.0 73.0 81.2
    Water flow (m³ /h) 10.3 9.3 12.5 14.7
    Heating capacity (kW) 6.0
    Humidification capacity (kg/h) 3.0
    Water resistance (kPa) 75.0 78.5 79.0 80.0
    Circulating Air Volume (CMH) 12000
    Number of fans 3
    Size: Width * Depth * Height (mm) 600*1200*2200
    主站蜘蛛池模板: 中国一级毛片 | 成人深夜| 图片区 偷拍区 小说区 视频 | 国外精品视频在线观看免费 | 黄色片成人免费观看 | 国产又色又爽又免费的刺激软件 | 曰本人做爰大片免费观看一 | 窝窝午夜看片 | 日本高清www | 男人猛躁进女人的毛片A片 男人猛躁进女人的毛片A片小说 | 99久久久无码欧美精品性 | 波多野结衣伦理在线观看 | 无码乱人伦一区二区亚洲一 | 午夜寂寞影| 在线观看日本视频免费 | youjizzxxxx18| 午夜视频入口 | 欧美性受xxxx| 综合激情区视频一区视频二区 | 日本无码一区二区三区不卡毛片 | 午夜亚洲影院在线观看 | 精品免费国产一区二区三区四区 | 中文在线最新版天堂 | 色影| 波多野结衣免费播放 | 全免费a级毛片免费看不卡 全免费a级毛片免费看 | 欧美成人天天综合在线视色 | 欧美aa级片 | 国精产品999一区二区三区有限 | 顶级毛片 | 99热在线看 | 日本理伦片午夜理伦片 | h视频免费 | 人人艹人人 | 狠狠躁夜夜躁人人爽天天段 | 天堂中文字幕在线 | 在线观看成人网 | 久久久久久久岛国免费播放 | 伊人成综合网伊人222 | 久热99这里只有精品视频6 | 永久久久免费人妻精品 |